• If a DHCP server is not found, the controller will
switch to Auto IP mode, in which it follows link-local
addressing for address resolution.
• It will acquire an IP address in the range 169.254.1.0
- 169.254.254.254. The controller will use the last
two characters of its serial number as the last octet
for starting address search. For example, if the serial
number ends with 36 (Conversion HexToDec = 54),
the IP address is set to 169.254.1.54).
• If the controller has link-local addressing, the
controller will periodically (every 1 minute) search for
the DHCP server. If a server is found, the controller
will acquire a new IP address from the server and
start using it immediately.
Subnet must be set to 255.255.0.0