TC500 - Change BACnet Space Temp and Setpoint Points to Celsius

Description:

By default, the TC500 BACnet space temp and setpoint points are imported with imperial units (Fahrenheit) with values to suit regardless of the unit setting of the device.

Procedure:

If importing new points to your database.
  1. Run a BACnet points discovery using a BACnet Point Manager view
  2. Select all the temperature points you require from the discovered pane and drag down into the database pane.
  3. Select all points in the popup
  4. Change the Facets to Celsius and Save

If modifying existing points in your database.
  1. Select all the temperature points you require from the database pane
  2. Click on the Edit button
  3. Select all points in the popup
  4. Change the Facets to Celsius and Save