Description:
The TC500 has afterhours functionality built in using the override button on the screen.
Procedure:
- Ensure the basic user has override privileges
- Navigate to Advanced> Miscellaneous> Unoccupied Override Time
- Set the value to between 0 and 1080min (Default 180min)
If controlling Via BACnet
The BACnet parameter to adjust is Cfg_Thermostat_BypOverrideTime (AV-10).
If connected to a BACnet network, override state and time remaining are also available parameters.